Fire Plan Review Checklist

Fire Site Plan Review (Fire Department Access)

  • Drawings signed and sealed.
  • FD access 20' clear width, 13'-6" height.
  • Coordination with hydrants and FDC.
  • Turnarounds for dead ends 150' or more in length.
  • Cul-de-sac min. inside diameter 36' and the min. outside diameter 60'.
  • FD access min. right hand turn radius 25'.
  • If the building set back more than 150' from the paved FD access, provide a fire lane.
  • If the building over 30' in height and setback more than 50' from the paved FD access, provide a fire lane.
  • Gates provide sufficient access width (20') and height (13'-6").
  • Automatic fence installed on 24-hour occupied structures; optical sensors.
  • Fence obstruction to hydrants, hose lay distance, FDC, egress path.